3 site altitude, Site altitude, 9mains and environment – Lenze DSD User Manual
Page 280

9
Mains and environment
9.2
Ambient conditions
280
Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.3
Site altitude
The components can be operated up to a site altitude of 1000 m amsl without power reduction.
• From 1000 ... 4000 m amsl there is a power reduction.
• For inverters the derating factor is stored in the DSD device-specifically.
• The site altitude for geared motors is considered as a function of the temperature:
• For motors without a gearbox, the following applies:
ϑ
opr
k
h
≤ 1000 m
≤ 2000 m
≤ 3000 m
≤ 4000 m
20 °C
1.15
1.04
0.92
0.81
30 °C
1
0.9
0.8
0.70
40 °C
0.8
0.72
0.64
0.56
50 °C
0.6
0.54
0.48
0.42
60 °C
0.4
0.36
0.32
0.28
h
k
h
0 ... 1000 m
1
≤ 2000 m
0.95
≤ 3000 m
0.9
≤ 4000 m
0.85