Xtra-guard® 4 – Northern Connectors Alpha Wire XTRA-GUARD Performance Cable User Manual

Page 57

Advertising
background image

Alpha Wire | www.alphawire.com | 1-800-52 ALPHA

Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.

85

Cable > Xtra-Guard > Xtra-Guard 4 > Multiconductor > Foil Shielded > 600 V

Xtra-Guard® 4

Advanced Temperature and Chemical Performance

600 V Foil Shielded, Multiconductor

UL AWM 20238

UL TC, WTTC

CSA AWM I/II A/B FT1

MSHA P-07-KA070017-MSHA

NEC Class 1, Div 2

Operating Temperature

• –50°C to +125°C

Conductor Color Coding

• Chart E (page 520)

• Nine jacket colors

(black standard)

• Custom colors available

Materials

• Stranded tinned copper

conductors

• TPE insulation

• TPE jacket

• Aluminum/polyester foil shield,

with 25% overlap and foil

facing inward

• Tinned copper drain wire sized

the same as cable conductors

• Nylon ripcord

Availability

Made to order

1000 ft (305 m) minimum

FIT® Tubing Recommendations

• FIT-600: highly flexible,

cross-linked elastomer

• FIT-400: temperature/chemical

resistant FEP

18 AWG (0.81 mm

2

)

Stranding: 16/30 (16 x 0.25 mm)

Insulation thickness: 0.032 (0.81 mm)

Part No.

Conductors

Nominal Diameter

Jacket Thickness

Inch

mm

Inch

mm

45430/2

2

0.340

8.64

0.055

1.40

45430/3

3

0.357

9.07

0.055

1.40

45430/4

4

0.387

9.83

0.055

1.40

45430/5

5

0.420

10.67

0.055

1.40

45430/7

7

0.454

11.53

0.055

1.40

45430/9

9

0.543

13.79

0.055

1.40

45430/12

12

0.599

15.21

0.065

1.65

16 AWG (1.23 mm

2

)

Stranding: 19/0.0117 (19 x 0.29 mm)

Insulation thickness: 0.032 (0.81 mm)

Part No.

Conductors

Nominal Diameter

Jacket Thickness

Inch

mm

Inch

mm

45440/2

2

0.364

9.25

0.055

1.40

45440/3

3

0.383

9.73

0.055

1.40

45440/5

5

0.452

11.48

0.055

1.40

45440/7

7

0.490

12.45

0.055

1.40

45440/9

9

0.587

14.91

0.065

1.65

45440/12

12

0.649

16.48

0.065

1.65

14 AWG (2.08 mm

2

)

Stranding: 41/30 (41 x 0.25 mm)

Insulation thickness: 0.032 (0.81 mm)

Part No.

Conductors

Nominal Diameter

Jacket Thickness

Inch

mm

Inch

mm

45450/2

2

0.394

10.01

0.055

1.40

45450/3

3

0.416

10.57

0.055

1.40

45450/5

5

0.493

12.52

0.055

1.40

45450/7

7

0.555

14.10

0.065

1.65

45450/15

15

0.775

19.69

0.065

1.65

Advertising