SATEC EM720 Operation Manual User Manual

Page 122

Advertising
background image

Chapter 5 Configuring the EM720

Configuring Communication Protocols

122

EM720 Power Quality and Revenue Meter

Parameter Options

Default

Description

Analog Input Object

32-bit
32-bit –Flag
16-bit
16-bit –Flag

16-bit -Flag

The default AI object variation for
requests with qualifier code 06
when no specific variation is

requested

Analog Input Change
Event Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

16-bit +Time The default AI change event object

variation for requests with qualifier
code 06 when no specific variation

is requested

Binary Counters (BC)

Number of BC to Generate
events

0-64

3

0

The total number of BC change
event points for monitoring

Binary Counter Object

32-bit +Flag
32-bit –Flag
16-bit +Flag
16-bit –Flag

32-bit -Flag

The default BC object variation for
requests with qualifier code 06
when no specific variation is

requested

Binary Counter Change

Event Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

32-bit +Time The default BC change event

object variation for requests with
qualifier code 06 when no specific
variation is requested

Frozen Binary Counter

Object

32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time

32-bit -Flag

The default frozen BC object
variation for requests with qualifier
code 06 when no specific variation

is requested

DNP General Options

16-bit AI Scaling

Disabled
Enabled

Enabled

Allows scaling 16-bit analog input
objects (see description below)

16-bit BC Scaling

x1, x10,
x100, x1000

x1

Allows scaling 16-bit binary
counter objects (see description

below)

Re-mapping Event Points Disabled

Enabled

Disabled

Allows re-mapping event points
starting with point 0.

SBO Timeout

1

2-30 sec

10

Defines the Select Before Operate
(SBO) timeout when using the

Control-Relay-Output-Block object

Time Sync Period

2

0-86400 sec

86400

Defines the time interval between
periodic time synchronization

requests

Multi Fragment Interval

50-500 ms

50

Defines the time interval between
fragments of the response

message when it is fragmented

1

The Select Before Operate command causes the device to

start a timer. The following Operate command must be sent

before the specified timeout value expires.

2

The device requests time synchronization by bit 4 in the

first octet of the internal indication word being set to 1 when the

time interval specified by the Time Sync Period elapses. The
master should synchronize the time in the device by sending the

Time and Date object to clear this bit. The device does not send

time synchronization requests if the Time Sync Period is set to 0.

3

The total number of AI, BI and BC change event points may

not exceed 64. When you change the number of the change

event points in the device, all event setpoints are set to defaults

(see Configuring DNP Event Classes below).

Advertising