Chapter 5 Configuring the EM720

General Meter Setup

EM720 Power Quality and Revenue Meter

73

Instrument Transformer Correction Setup

Transformer correction allows you to compensate ratio and
phase angle inaccuracies of the voltage and current
instrument transformers.

Select General Setup from the Meter Setup menu, and then
click on the Transformer Correction tab.

The available options are listed in the following table.

Parameter Options

Description

Channel

None, V1-V3, I1-I4 Voltage/current

channel

Test Point, %

5-200%

Percent of the nominal (rated) voltage/current at
which the ratio correction factor and phase angle

error are specified

Ratio Correction Factor

0.900-1.100

The ratio of the true transformer ratio to the
marked ratio

Phase Angle Error

+/-600 minutes

The phase displacement, in minutes, between
the primary and secondary values. The phase
angle of a transformer is positive when the

secondary value leads the primary value.

You can define a total of 56 correction points for ratio and
phase correction data - up to 8 test points per voltage and
current channel, based on the transformer’s accuracy
characteristics. If more than one test point is given for a
channel, the meter dynamically interpolates to the actual
operating point depending on the measured voltage or
current. When a single test point is defined, it is applied over
the full operating range of the transformer.