Chapter 2 Operating the EM720

TEST Mode

EM720 Power Quality and Revenue Meter

15

Rated Voltage,

V

Secondary

Current, A

Pulse Rate,

imp/kWh

57-120 1 20,000
57-120 5

4,000

120-277 1

12,500

120-277 5

2,500

The LED pulse rate in TEST mode is user-programmable. The
factory set defaults and available ranges are shown in the
following table.

Rated

Voltage, V

Secondary

Current, A

Default Pulse Rate,

imp/kWh (Wh/imp)

Range,

imp/kWh (Wh/imp)

57-120

1

20,000 (0.05)

20,000-100,000 (0.01-0.05)

57-120

5

10,000 (0.10)

4,000-100,000 (0.01-0.25)

120-277

1

20,000 (0.05)

12,500-100,000 (0.01-0.08)

120-277

5

10,000 (0.10)

2,500-100,000 (0.01-0.40)

See

Device Options and Mode Control

in Chapter 5 on how to

change the LED pulse rate in your meter.

TEST Mode

The EM720 can run in NORMAL or in TEST mode.

TEST mode is intended for testing the device energy
measurement accuracy without affecting the billing energy
and demand data. All instrumentation data is still available in
TEST mode.

The front pulse LED indicators flash at a programmable rate
in TEST mode, and the billing data display shows separate
test kWh and kvarh energy readings with an extended 0.001
kWh resolution.

See

Device Options and Mode Control

in Chapter 5 on how to

put your meter in TEST mode and to change the test LED
pulse rate. See

TEST Mode Data Display

for more information

on the TEST mode display.

NOTE

In TEST mode the following features are not operational:

• setpoints

• power quality recorder

• fault recorder

• relay outputs

• instrument transformer correction

• transformer/line loss compensation

Device Diagnostics

Device diagnostic messages may appear as a result of the
EM720 built-in diagnostic tests performed during start-up and
device operation.

A blinking diagnostics indicator is shown on the display
whenever there are diagnostic messages. See

Status