Chapter 5 Configuring the EM720

General Meter Setup

76

EM720 Power Quality and Revenue Meter

Billing Point


Metering Point

Supply side,
far end

Supply side,
transformer end

Load side,
transformer end

Load side,
far end

Supply side,
far end

-Supply line losses

-Supply line losses
-Transformer losses

-Supply line losses
-Transformer losses
-Load line losses

Supply side,
transformer end

+Supply line losses

-Transformer losses -Transformer losses

-Load line losses

Load side,
transformer end

+Supply line losses
+Transformer losses

+Transformer losses

-Load line losses

Load side,
far end

+Supply line losses
+Transformer losses
+Load line losses

+Transformer losses
+Load line losses

+Load line losses

4. Select the number of metering elements depending on

the wiring mode set in the meter. It is not a critical
parameter and the actual losses will not be affected by
this setting.

5. Specify the power transformer data. It is normally

taken from the transformer nameplate and
transformer datasheet. All transformer data is given
for a 3-phase system.

6. If the supply-side or/and load-side power line losses

are to be included in compensation, specify the length
of power lines and their resistance and reactance per
mile or km. To change the length units, select Options
from the Tools menu, click on the Preferences tab, and
then check the preferred distance units.

7. After all data is specified, click on the Calculate %Loss

Constants button to update the loss constants.

8. Select Enable in the Loss Compensation Enabled box to

enable loss compensation in the meter.

9. Send your new setup to the meter.

NOTE

You can also enable and disable loss compensation via the
front display (see

Device Options and Mode Control

).

Local Settings

This setup allows you to specify your local time zone, daylight
saving time options and time synchronization source.

Using the Front Display

Select Local from the main menu. See

Viewing and Changing

Setup Options

in Chapter 3 for information on navigating in

menus.

See the table below for available options.

Using PAS

Select General Setup from the Meter Setup menu, and then
click on the Local Settings tab.