Chapter 5 Configuring the EM720

Configuring Billing/TOU

EM720 Power Quality and Revenue Meter

95

Parameter Options Default

Description

Channel

No, Ch1-Ch6

None

Defines a measurement channel for multi-
meter energy metering. Not used for a
single self-metering channel if there are no
external sources. Set to Ch1 for internal
energy sources, and to Ch2 through Ch6 for
external sources in the event of multi-

channel energy metering.

Register Source List

Source
Input

None
kWh IMPORT
KWh EXPORT
kvarh IMPORT
kvarh EXPORT
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
kVAh TOTAL
kVAh IMPORT
kVAh EXPORT
DI1-DI8

None

Links an internal or external energy source
to the billing register.

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy

source. Not effective for internal sources.

Target

Reg#1- Reg#10

None

Defines the target billing register for the

energy source. It is set automatically.

Configuring the Daily Tariff Schedule

To configure your daily tariff schedule, select Energy/TOU
from the Meter Setup menu, and then click on the TOU Daily
Profiles tab.