Chapter 5 Configuring the EM720

Configuring Communication Protocols

EM720 Power Quality and Revenue Meter

125

The number of event setpoints for each static object type is
specified via the

DNP Options

setup.

NOTE

The device clears all event buffers and links the default set of
static points to each event object type every time you change
the number of points for any of the objects.

To define setpoints for selected static points:

1. Check the “Ext” box if you wish to use the extended

point list.

2. Select a parameter group and then a desired

parameter for each event point.

3. For AI and BC points, select a relation and an

operating threshold or a deadband to be used for
detecting events. All thresholds are specified in
primary units. The following relations are available:

• Delta – a new event is generated when the absolute

value of the difference between the last reported point
value and its current value exceeds the specified

deadband value;

• More than (over) - a new event is generated when the

point value rises over the specified threshold, and
then when it returns below the threshold minus a

predefined return hysteresis – applicable for AI

objects;

• Less than (under) - a new event is generated when

the point value drops below the specified threshold,

and then when it returns above the threshold plus a