Chapter 9 Viewing Files and Reports

Viewing Waveforms

168

EM720 Power Quality and Revenue Meter

Waveform Viewing Options

See

Working with Graphic Windows

for more information on

working with waveforms.

Viewing Phasor Diagrams

The phasor diagrams show you relative magnitudes and
angles of the three-phase voltage and current fundamental
component. All angles are shown relative to the reference
voltage channel.

To change the reference channel, click on the waveform
window with the right mouse button, select “Options...”, click
on the “Phasor” tab, check the channel you want to make a
reference channel, and then click “OK”.

If you leave the Triangle box checked, PAS connects the ends
of the voltage and current vectors showing you three-phase
voltage and current triangles. This is useful when analyzing
voltage and current unbalances.

Phasor diagrams are calculated over one waveform cycle
pointed to by the left marker line. As you move the marker,
the phasor diagrams are updated reflecting the new marker
position.

Viewing Symmetrical Components

Waveform views have an additional pane at the right where
PAS displays the symmetrical components for voltages and