Debounce time – SATEC EM720 Operation Manual User Manual

Page 83

Advertising
background image

Chapter 5 Configuring the EM720

General Meter Setup

EM720 Power Quality and Revenue Meter

83

Parameter Options Default

Description

Debounce time

1-1000 ms

10 ms

The amount of time while the state of the
digital input should not change to be
recognized as a new state. Too low
debounce time could produce multiple

events on the input change.

Fault Recorder

Checked
Unchecked

Unchecked

When the box is checked, a positive
transition on the digital input (open to
closed transition event) triggers the Fault

recorder.

Debounce Time

The debounce time is assigned in groups of 2 adjacent digital
inputs. DI1 and DI2 have the same debounce time, while DI3
and DI4 are allowed to have another setting. If you change
the debounce time for a digital input, the same debounce
time is automatically assigned to the second input in the
same group.

Triggering the Fault Recorder through Digital Inputs

Check the Fault recorder boxes for digital inputs you wish to
use as triggers for the Fault recorder.

When an open-to-closed state transition is detected on the
digital input, the global “External Trigger” event is generated
in the meter. If the external triggers are enabled in the Fault
recorder (see

Configuring the Fault Recorder

), it triggers the

recorder to record waveforms or RMS data profile for the
event.

When a number of digital inputs linked to the Fault recorder
are operated at the same time, only the first triggers the
Fault recorder and logs a fault event into the Fault log file.
The next external fault event is not triggered until all digital
inputs linked to the Fault recorder are released. This does not
affect operations of the internal analog fault triggers that
work independently.

Notice that the “External Trigger” event can also be tested
through the control setpoints from the “Static Events” trigger
group to trigger another action on your selection.