Chapter 5 Configuring the EM720

Configuring Billing/TOU

94

EM720 Power Quality and Revenue Meter

Configuring Billing/Tariff Registers

Select Energy/TOU from the Meter Setup menu.

The available options are shown in the following table:

Parameter Options Default

Description

Billing/TOU Registers

TOU Unchecked

Checked

Unchecked

Links multi-tariff registers to the selected
energy source

Use Profile

Unchecked
Checked

Checked

Enables recording energy registers in
monthly/daily billing profile files (both total
and tariff registers if TOU is enabled).
Always enabled for all configured billing

registers.

Dmd Profile Unchecked

Checked

Unchecked

Enables recording maximum demand
registers in monthly/daily billing profile files
(both total and tariff registers if TOU is

enabled)

Sum Profile Unchecked

Checked

Checked

Enables recording total (summary) registers
in monthly/daily billing profile files. Always

enabled for all configured billing registers.

Units None

kWh+ (import)
kWh- (export)
kvarh+ (import)
kvarh- (export)
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
kVAh (total)
kVAh+ (import)
kVAh- (export)

None

The register measurement unit.
Selected automatically for registers linked

to internal energy sources.
Select an appropriate measurement unit for
external pulse sources.