Chapter 5 Configuring the EM720

General Meter Setup

74

EM720 Power Quality and Revenue Meter

The order in which you define the test points does not
matter. The meter will automatically arrange all data in a
correct order.

Check the Correction Enabled box to activate transformer
correction in the meter. You can also enable and disable
transformer correction from the front display (see

Device

Options and Mode Control

).

Transformer/Line Loss Compensation Setup

Loss compensation corrects the power and energy readings of
the meter when the metering point and point of billing are
physically separated by a power transformer or a power line.

Select General Setup from the Meter Setup menu, and then
click on the Transformer/Line Loss Compensation tab.

The available options are described in the following table.

Parameter Options

Description

Metering and Location

Loss Compensation Enabled

Disabled, Enabled

Enables/disables loss compensation

Metering Point Location

Supply side, far end,
Supply side,
transformer end,
Load side,
transformer end,
Load side, far end

Defines the location of the meter:
far end – near the supply source or near the load,
transformer end – near the power transformer.