Appendix A Parameters for Monitoring and Logging

192

EM720 Power Quality and Revenue Meter

Designation Description

V2 Chg%

V2 Voltage change, %Un (last 1-hour value)

V2 Chg Freq

Repetition rate of V2 voltage changes, 1/min

V3 Chg%

V3 Voltage change, %Un (last 1-hour value)

V3 Chg Freq

Repetition rate of V3 voltage changes, 1/min

V1 Pst

V1 Voltage Pst

V2 Pst

V2 Voltage Pst

V3 Pst

V3 Voltage Pst

V1 Plt

V1 Voltage Plt

V2 Plt

V2 Voltage Plt

V3 Plt

V3 Voltage Plt

V1 THD

V1 Voltage THD, %

V2 THD

V2 Voltage THD, %

V3 THD

V3 Voltage THD, %

NSeq Unb%

Negative-sequence voltage unbalance, % (last 10-min value)

Freq Var

Frequency variation, +/-Hz (last 10-s value)

1

In 4LN3, 4LL3, 3LN3 and 3LL3 wiring modes, the voltages are

line-to-neutral; for any other wiring mode, they are line-to-line

voltages.

2

In 4LN3 and 3LN3 wiring modes, the voltages are line-to-

neutral; for any other wiring mode, they are line-to-line

voltages.

3

On a 0.2-s interval

.

4

On a 3-s interval.

5

On a 10-s interval.

6

The value is calculated using a simplified technique as a

relation of the maximum deviation of phase values from a 3-
phase average value to a 3-phase average.

7

The value is calculated using a simplified technique as a

one third of the RMS value of a 3-phase vector sum.

8

Not affected by loss compensation – always indicate

readings at the metering point.

NOTE

Designations of some enginering demands and billing energy
and demand registers are shown using a new short name
notation available in PAS V1.4. By default, PAS uses long
names compatible with older versions of PAS. You can select
a desired notation from the Tools/Options/Preferences tab.

PAS does not allow to store data in files using different data
names. If you have a file uploaded with a previous version of
PAS using long data names, either continue using long data
names, or store data in a new file.

See table below for a list of parameters with short and long
names.

Short Data

Name

Long Data Name

Description

kW IMP ACD

kW IMP ACC DMD

Accumulated demand

kW IMP PRD

kW IMP PRD DMD

Predicted sliding window demand

PF IMP@kVA MD PF IMP@kVA MXDMD

PF (import) at maximum kVA demand

REG1 ACD

SUM REG1 ACC DMD

Billing summary (total) register accumulated demand