Chapter 5 Configuring the EM720

Configuring Communications

EM720 Power Quality and Revenue Meter

61

Display

Label

Parameter Options Default

Description

Protocol Communication

protocol

Modbus RTU,
Modbus ASCII,
DNP3,
IEC 62056-21

IEC 62056-21

(COM1)
Modbus RTU
(COM 3)

The communications

protocol for the port

Interface

Port interface

RS232, RS485,
IR, GPRS

IR (COM1)
GPRS (COM2)
RS485 (COM3)

Not changeable;
automatically detected by

the meter

Address

Device address Modbus: 1-247

DNP3: 0-65532
IEC 62056-21:

0-65532

1

Device network address

Baud Rate

Baud rate

COM1: 300-

19200 kbps,
COM2-3: 300-
115.2 kbps

19.2 kbps

The port baud rate

Data/Parity Data

format

and parity

7E, 8N, 8E

8N

7E data format should not
be used with the Modbus

RTU and DNP3 protocols

Send Delay

Response delay 0-1000 ms

5 ms

The minimum time after the
last request character is
received to start the

transmission.

Chr.Timeout Character

timeout

0-1000 ms

4 ms

The maximum time the line
is allowed to idle before
closing a connection in the
Modbus RTU and DNP3

protocols

The meter automatically detects replaceable communication
modules and does not allow you to change the baud rate and
data format for the Dial-up GSM/GPRS modem.