Parámetros de Grupo Avanzados

No. Parámetro

Mín./máx.

Pantalla/opciones

Opción

predeterminada

en la fábrica

A051

A052

A053

A054

[Sel. ent digt 1]

terminal de E/S 05

[Sel. ent digt 2]

terminal de E/S 06

[Sel. ent digt 3]

terminal de E/S 07

[Sel. ent digt 4]

terminal de E/S 08

0/27

0 = “Not Used”

1 = “Acc & Dec 2”

2 = “Jog”

3 = “Aux Fault”

4 = “Preset Freq”

5 = “Local”

(1)

6 = “Comm Port”

7 = “Clear Fault”

8 = “RampStop,CF”

9 = “CoastStop,CF”

10 = “DCInjStop,CF”

11 = “Jog Forward”

12 = “Jog Reverse”

13 = “10 V In Ctrl”

14 = “20 mA In Ctrl”

15 = “PID Disable”

16 = “MOP Up”

17 = “MOP Down”

18 = “Timer Start”

19 = “Counter In”

20 = “Reset Timer”

21 = “Reset Countr”

22 = “Rset Tim&Cnt”

23 = “Logic In1”

24 = “Logic In2”

25 = “Current Lmt2”

26 = “Anlg Invert”

27 = “EM Brk Rlse”

4

4

5

11

(1)

Importante: La fuente de velocidad para

los variadores con clasificación IP66,

NEMA/UL Tipo 4X proviene de A069

[Internal Freq].

A055 [Sel. Sal. Relé]

0/24

0 = “Ready/Fault”

1 = “At Frequency”

2 = “MotorRunning”

3 = “Reverse”

4 = “Motor Overld”

5 = “Ramp Reg”

6 = “Above Freq”

7 = “Above Cur”

8 = “Above DCVolt”

9 = “Retries Exst”

10 = “Above Anlg V”

11 = “Logic In 1”

12 = “Logic In 2”

13 = “Logic 1 & 2”

14 = “Logic 1 or 2”

15 = “StpLogic Out”

16 = “Timer Out”

17 = “Counter Out”

18 = “Above PF Ang”

19 = “Anlg In Loss”

20 = “ParamControl”

21 = “NonRec Fault”

22 = “EM Brk Cntrl”

23 = “Above Fcmd”

24 = “CntrlMens” (Para

FRN 6.01 y posterior)

0

A056 [Relay Out Level]

0.0/9999

0.1

0.0

A058

A061

[Sel Sal Óptica 1]

[Sel Sal Óptica 2]

0/24

Vea A055 para las opciones.

2

1

A059

A062

[Opto Out1 Level]

[Opto Out2 Level]

0.0/9999

0.1

0.0

A064 [Opto Out Logic]

0/3

1

0

Ajuste A055, A058 y A061

A056, A059 y A062 mín/máx

6

0/400 Hz

7

0/180 %

8

0/815 Volts

10

0/100 %

16

0.1/9999 segundos

17

1/9999 conteos

18

1/180 grados

20

0/1

23

0/400 Hz

Opción A064

Lógica Out1 óptica

Lógica Out2 óptica 2

0

NA (normalmente abierto)

NA (normalmente abierto)

1

NC (normalmente cerrado)

NA (normalmente abierto)

2

NA (normalmente abierto)

NC (normalmente cerrado)

3

NC (normalmente cerrado)

NC (normalmente cerrado)

Consulte el documento PowerFlex 40 User Manual para más información sobre parámetros.