English-14

The PowerFlex 40 is designed so that start up is simple and efficient. The Program Group

contains the most commonly used parameters.

Display Group Parameters

No. Parameter

Min/Max

Display/Options

d001 [Output Freq]

0.0/[Maximum Freq]

0.1 Hz

d002 [Commanded Freq]

0.0/[Maximum Freq]

0.1 Hz

d003 [Output Current]

0.00/(Drive Amps

× 2)

0.01 Amps

d004 [Output Voltage]

0/Drive Rated Volts

1 VAC

d005 [DC Bus Voltage]

Based on Drive Rating

1 VDC

d006 [Drive Status]

0/1 (1 = Condition True)

Bit 3

Bit 2

Bit 1

Bit 0

Decelerating

Accelerating

Forward

Running

d007-

d009

[Fault x Code]

F2/F122

F1

d010 [Process Display]

0.00/9999

0.01 – 1

d012 [Control Source]

0/9

Digit 1 = Speed Command

Digit 0 = Start Command

(See P038; 9 = “Jog Freq”)

(See P036; 9 = “Jog”)

d013 [Contrl In Status]

0/1 (1 = Input Present)

Bit 3

Bit 2

Bit 1

Bit 0

DB Trans On

Stop Input

Dir/REV In

Start/FWD In

d014 [Dig In Status]

0/1 (1 = Input Present)

Bit 3

Bit 2

Bit 1

Bit 0

Digital In 4

Digital In 3

Digital In 2

Digital In 1

d015 [Comm Status]

0/1 (1 = Condition True)

Bit 3

Bit 2

Bit 1

Bit 0

Comm Error

DSI Option

Transmitting

Receiving

d016 [Control SW Ver]

1.00/99.99

0.01

d017 [Drive Type]

1001/9999

1

d018 [Elapsed Run Time]

0/9999 Hrs

1 = 10 Hrs

d019 [Testpoint Data]

0/FFFF

1 Hex

d020 [Analog In 0-10V]

0.0/100.0%

0.1%

d021 [Analog In 4-20mA]

0.0/100.0%

0.1%

d022 [Output Power]

0.00/(Drive Power

× 2)

0.01 kW

d023 [Output Powr Fctr]

0.0/180.0 deg

0.1 deg

d024 [Drive Temp]

0/120 degC

1 degC

d025 [Counter Status]

0/9999

1

d026 [Timer Status]

0.0/9999 Secs

0.1 Secs

d028 [Stp Logic Status]

0/7

1

d029 [Torque Current]

0.00/(Drive Amps

× 2)

0.01 Amps

Smart Start-Up with Basic Program Group Parameters

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

P031 [Motor NP Volts]

20/Drive Rated Volts

1 VAC

Based on Drive Rating

Set to the motor nameplate rated volts.

P032 [Motor NP Hertz]

15/400 Hz

1 Hz

60 Hz

Set to the motor nameplate rated frequency.

P033 [Motor OL Current]

0.0/(Drive Rated Amps

× 2) 0.1 Amps

Based on Drive Rating

Set to the maximum allowable motor current.

P034 [Minimum Freq]

0.0/400.0 Hz

0.1 Hz

0.0 Hz

Sets the lowest frequency the drive will output

continuously.

P035 [Maximum Freq]

0/400 Hz

1 Hz

60 Hz

Sets the highest frequency the drive will output.

P036 [Start Source]

0/6

0 = “Keypad”

(1)

1 = “3-Wire”

2 = “2-Wire”

3 = “2-W Lvl Sens”

4 = “2-W Hi Speed”

5 = “Comm Port”

6 = “Momt FWD/REV”

0

Sets the control scheme used to start the drive.

(1)

When active, the Reverse key is also active

unless disabled by A095 [Reverse Disable].

See the PowerFlex 40 User Manual for more information on parameters.