Input/Output Ratings

Approvals

Output Frequency: 0-400 Hz (Programmable)
Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6mA)

Analog Control Inputs

SRC (Source) Mode:

18-24V = ON

0-6V = OFF

SNK (Sink) Mode:

0-6V = ON

18-24V = OFF

4-20mA Analog: 250 ohm input impedance

0-10V DC Analog: 100k ohm input impedance

External Pot: 1-10k ohms, 2 Watt minimum

Control Output

Programmable Output (form C relay)

Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC

Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

Opto Outputs

30V DC, 50mA

Non-inductive

Analog Outputs (10 bit)

0-10V, 1k ohm Min.

4-20mA, 525 ohm Max.

Fuses and Circuit Breakers

Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

Recommended Circuit Breakers: HMCP circuit breakers or equivalent.

Protective Features

Motor Protection: I2t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage: 100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)

200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)

380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

460-600V AC Input – Trip occurs at 1005V DC bus voltage (equivalent to 711V AC incoming line)

Under Voltage: 100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)

200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)

380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

460-600V AC Input – If P042 = 3 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);

If P042 = 2 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 40 User Manual

for DB resistor ordering information.

UL

®

LIST

ED 966X

IND CONT EQ

UL508C

UL

®

LIST

ED 966X

IND CONT EQ

C

CSA 22.2

EMC Directive 89/336

LV:

EN 50178, EN 60204

EMC: EN 61800-3, EN 50081-1, EN 50082-2