Nederlands-19 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 133

Advertising
background image

Nederlands-19

A117 [Busreg.modus]

0/1

0 = “Uit”

1 = “Vrijgegeven”

1

A118 [Stroomgrens 2]

0,1/(A van drive

× 1,8) 0,1 A

A

× 1,5

A119 [Skip Frequency]

0/400 Hz

1 Hz

0 Hz

A120 [Skip Freq Band]

0,0/30,0 Hz

0,1 Hz

0,0 Hz

A121 [Stall Fault Time]

0/5

0 = “60 sec”

1 = “120 sec”

2 = “240 sec”

3 = “360 sec”

4 = “480 sec”

5 = “Fout uit”

0

A122 [Verlies anal ing]

0/6

0 = “Uit”

1 = “Fout (F29)”

2 = “Stoppen”

3 = “Ref nul”

4 = “Ref min freq”

5 = “Ref max freq”

6 = “Ref int freq”

0

A123 [10 V bipol vrijg]

0/1

0 = “Unipolair in”

1 = “Bipolair in”

0

A124 [Var PWM uit]

0/1

0 = “Vrijgegeven”

1 = “Uit”

0

A125 [Koppel prestatie mode] 0/1

0 = “V/Hz”

1 = “Sensrlz vect”

1

A126 [Motorstroom]

0,1/(A van drive

× 2) 0,1 A

Nominale A

A127 [Autotune]

0/2

0 = “Gereed/Idle”

1 = “Stat tunen”

2 = “Dynamisch tunen”

0

A128 [Spanningsval IR]

0,0/230,0 VAC

0,1 VAC

Nominale V

A129 [Fluxstroomref]

0,00/[Motorstroom]

0,01 A

Nominale A

A130 [PID trim hoog]

0.0/400.0

0.1

60.0

A131 [PID trim laag]

0.0/400.0

0.1

0.0

A132 [Sel PID ref]

0/8

0 = “PID uit”

1 = “PID setpunt”

2 = “0 – 10 V ing”

3 = “4 – 20 mA ing”

4 = “Comm.poort”

5 = “Setpnt, trim”

6 = “0 – 10 V, trim”

7 = “4 – 20 mA, trim”

8 = “Comm, trim”

0

A133 [Sel PID feedback]

0/2

0 = “0 – 10 V ing”

1 = “4 – 20 mA ing”

2 = “Comm.poort”

0

A134 [PID prop verst]

0.00/99.99

0.01

0.01

A135 [PID integ tijd]

0,0/999,9 Secs

0,1 sec

0,1 sec

A136 [PID diff snelh]

0,00/99,99 (1/sec)

0,01 (1/sec)

0,01 (1/sec)

A137 [PID setpunt]

0,0/100,0%

0,1%

0,0%

A138 [PID dode zone]

0,0/10,0%

0,1%

0,0%

A139 [PID voorbel]

0,0/400,0 Hz

0,1 Hz

0,0 Hz

A140-

A147

[Stp Logic 0 – 7]

0001/bAFF

4 cijfers

Raadpleeg de Gebruikershandleiding van de

PowerFlex 40 voor een lijst met cijferopties.

00F1

A150-

A157

[Stp Logic Time 0 – 7] 0,0/999,9 Secs

0,1 sec

30,0 sec

A160 [Vrtr EM rem uit]

0,01/10,00 Secs

0,01 sec

2,00 sec

A161 [Vrtr EM rem aan]

0,01/10,00 Secs

0,01 sec

2,00 sec

A162 [Sel MOP reset]

0/1

0 = “MOP ref nul”

1 = “Save MOP ref”

1

A163 [DB drempel]

0,0/110,0%

0,0%

100,0%

A164 [Comm.schrijfmodus]

0/1

0 = “Opslaan”

1 = “Alleen RAM”

0

A165 [Vrtrag anl verls]

0,0/20,0 Secs

0,1 sec

0,0 sec

A166 [Anal ing filter]

0/14

1

0

A167 [PID Invert Fout]

0/1

0 = “Niet inverted”

1 = “Inverted”

0

Nr.

Parameter

Min/Max

Display/Opties

Default

Zie de gebruikershandleiding van de PowerFlex 40 voor meer informatie over parameters.