Nederlands-17, Nr. parameter min/max display/opties default – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 131

Advertising
background image

Nederlands-17

A065 [Sel anal uitg]

0/23

1

0

A066 [Anal uitg hoog]

0/800%

1%

100%

A067 [Accel.tijd 2]

0,0/600,0 sec

0,1 sec

20,0 sec

A068 [Decel.tijd 2]

0,1/600,0 sec

0,1 sec

20,0 sec

A069 [Interne freq]

0,0/400,0 Hz

0,1 Hz

0,0 Hz (voor

IP66, NEMA/

UL Type 4X

drives)

60,0 Hz (voor

IP20-drives)

A070

A071

A072

A073

A074

A075

A076

A077

[Preset freq 0]

(1)

[Preset freq 1]

[Preset freq 2]

[Preset freq 3]

[Preset freq 4]

[Preset freq 5]

[Preset freq 6]

[Preset freq 7]

0,0/400,0 Hz

0,1 Hz

0,0 Hz

5,0 Hz

10,0 Hz

20,0 Hz

30,0 Hz

40,0 Hz

50,0 Hz

60,0 Hz

(1)

Om [Preset Freq 0] te activeren P038 [Speed Reference] instellen op optie 4.

A078 [Jog freq]

0,0/[Max frequentie]

0,1 Hz

10,0 Hz

A079 [Jog Accel/Decel]

0,1/600,0 sec

0,1 sec

10,0 sec

A080 [DC remtijd]

0,0/99,9 sec

0,1 sec

0,0 sec

Een instelling van 99,9 sec = Continu

A081 [DC remniveau]

0,0/(A van drive

× 1,8) 0,1 A

A

× 0,05

A082 [Sel DB weerstand]

0/99

0 = “Uit”

1 = “Norm RA wrst”

2 = “Gn bescherm”

3

99 = % van cyclus

0

A083 [S Curve %]

0/100%

1%

0% (Uit)

Nr.

Parameter

Min/Max

Display/Opties

Default

Optie

Uitvoerbereik

Minimale

uitgangswaarde

Maximale uitgangswaarde

[Anal uitg hoog]

Positie

DIP-schakelaar

0 “Uitfreq 0 – 10”

0 – 10 V

0 V = 0 Hz

P035 [Max frequentie]

0 – 10 V

1 “Uit str 0 – 10”

0 – 10 V

0 V = 0 A

200% nominale stroom van drive

0 – 10 V

2 “Uit V 0 – 10”

0 – 10 V

0 V = 0 V

120% nominale uitgangsspanning van drive 0 – 10 V

3 “Uit vrm 0 – 10”

0 – 10 V

0 V = 0 kW

200% nominaal vermogen van drive

0 – 10 V

4 “Testgeg 0 – 10”

0 – 10 V

0 V = 0000

65535 (Hex FFFF)

0 – 10 V

5 “Uitfreq 0 – 20”

0 – 20 mA

0 mA = 0 Hz

P035 [Max frequentie]

0 – 20 mA

6 “Uit str 0 – 20”

0 – 20 mA

0 mA = 0 A

200% nominale stroom van drive

0 – 20 mA

7 “Uit V 0 – 20”

0 – 20 mA

0 mA = 0 V

120% nominale uitgangsspanning van drive 0 – 20 mA

8 “Uit vrm 0 – 20”

0 – 20 mA

0 mA = 0 kW

200% nominaal vermogen van drive

0 – 20 mA

9 “Testgeg 0 – 20”

0 – 20 mA

0 mA = 0000

65535 (Hex FFFF)

0 – 20 mA

10 “Uit freq 4 – 20” 4 – 20 mA

4 mA = 0 Hz

P035 [Max frequentie]

0 – 20 mA

11 “Uit str 4 – 20”

4 – 20 mA

4 mA = 0 A

200% nominale stroom van drive

0 – 20 mA

12 “Uit V 4 – 20”

4 – 20 mA

4 mA = 0 V

120% nominale uitgangsspanning van drive 0 – 20 mA

13 “Uit vrm 4 – 20” 4 – 20 mA

4 mA = 0 kW

200% nominaal vermogen van drive

0 – 20 mA

14 “Testgeg 4 – 20” 4 – 20 mA

4 mA = 0000

65535 (Hex FFFF)

0 – 20 mA

15 “Uitkopp 0 – 10” 0 – 10 V

0 V = 0 A

200% nominale stroom van drive

0 – 10 V

16 “Uitkopp 0 – 20” 0 – 20 mA

0 mA = 0 A

200% nominale stroom van drive

0 – 20 mA

17 “Uitkopp 4 – 20” 4 – 20 mA

4 mA = 0 A

200% nominale stroom van drive

0 – 20 mA

18 “Setpunt 0 – 10” 0 – 10 V

0 V = 0%

100,0% Setpunt instelling

0 – 10 V

19 “Setpunt 0 – 20” 0 – 20 mA

0 mA = 0%

100,0% Setpunt instelling

0 – 20 mA

20 “Setpunt 4 – 20” 4 – 20 mA

4 mA = 0%

100,0% Setpunt instelling

0 – 20 mA

21 “Min freq 0 – 10” 0 – 10 V

0 V = Min. Freq

P035 [Max frequentie]

0 – 10 V

22 “Min freq 0 – 20” 0 – 20 mA

0 mA = Min. Freq

P035 [Max frequentie]

0 – 20 mA

23 “Min freq 4 – 20” 4 – 20 mA

4 mA = Min. Freq

P035 [Max frequentie]

0 – 20 mA

Ingangstoestand van

digit ing 1 (I/O

aansluitterminal 05)

Ingangstoestand van

digit ing 2 (I/O

aansluitterminal 06)

Ingangstoestand van

digitale ing 3 (I/O

aansluitterminal 07)

Frequentiebron

Gebruikte parameter

Accel / Decel(2)

0

0

0

[Preset freq 0]

[Accel.tijd 1] / [Decel.tijd 1]

1

0

0

[Preset freq 1]

[Accel.tijd 1] / [Decel.tijd 1]

0

1

0

[Preset freq 2]

[Accel.tijd 2] / [Decel.tijd 2]

1

1

0

[Preset freq 3]

[Accel.tijd 2] / [Decel.tijd 2]

0

0

1

[Preset freq 4]

[Accel.tijd 1] / [Decel.tijd 1]

1

0

1

[Preset freq 5]

[Accel.tijd 1] / [Decel.tijd 1]

0

1

1

[Preset freq 6]

[Accel.tijd 2] / [Decel.tijd 2]

1

1

1

[Preset freq 7]

[Accel.tijd 2] / [Decel.tijd 2]

(2) Wanneer een digitale ingang op “Accel 2 en Decel 2” wordt ingesteld, en de ingang actief is, gaat de ingang aan de instellingen

in deze tabel voorbij.

Zie de gebruikershandleiding van de PowerFlex 40 voor meer informatie over parameters.

Advertising