Español-17 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 109

Advertising
background image

Español-17

A065 [Sel. Sal. Anlg]

0/23

1

0

A066 [Sal. Anlg. Máx.]

0/800 %

1 %

100 %

A067 [Accel Time 2]

0.0/600.0 segundos

0.1 segundos

20.0 segundos

A068 [Decel Time 2]

0.1/600.0 segundos

0.1 segundos

20.0 segundos

A069 [Internal Freq]

0.0/400.0 Hz

0.1 Hz

0.0 Hz (para

variadores con

clasficicación

IP66, NEMA/UL

Tipo 4X)

60.0 Hz (para

variadores con

clasificación IP20)

A070

A071

A072

A073

A074

A075

A076

A077

[Preset Freq 0]

(1)

[Preset Freq 1]

[Preset Freq 2]

[Preset Freq 3]

[Preset Freq 4]

[Preset Freq 5]

[Preset Freq 6]

[Preset Freq 7]

0.0/400.0 Hz

0.1 Hz

0.0 Hz

5.0 Hz

10.0 Hz

20.0 Hz

30.0 Hz

40.0 Hz

50.0 Hz

60.0 Hz

(1)

Para activar [Preset Freq 0] establezca P038 [Speed Reference] en la opción 4.

A078 [Jog Frequency]

0.0/[Maximum Freq]

0.1 Hz

10.0 Hz

A079 [Jog Accel/Decel]

0.1/600.0 segundos

0.1 segundos

10.0 segundos

A080 [DC Brake Time]

0.0/99.9 segundos

0.1 segundos

0.0 segundos

Una configuración de 99.9 segundos =

Continuo

A081 [DC Brake Level]

0.0/(Intens.Var

× 1.8) 0.1 Amps

Amps

× 0.05

A082 [DB Resistor Sel]

0/99

0 = “Disabled”

1 = “Normal RA Res”

2 = “NoProtection”

3–99 = % de ciclo de

servicio

0

No. Parámetro

Mín./máx.

Pantalla/opciones

Opción

predeterminada

en la fábrica

Opción

Rango de salida

Valor de salida

mínimo

Valor de salida máximo

[Sal. Anlg. Máx.]

Posición del

microinterruptor

0 “OutFreq 0–10”

0–10 V

0 V = 0 Hz

P035 [Maximum Freq]

0–10 V

1 “OutCurr 0–10”

0–10 V

0 V = 0 Amps

200 % Amp carga plena del variador

0–10 V

2 “OutVolt 0–10”

0–10 V

0 V = 0 Volts

120 % Volts salida nominal del variador 0–10 V

3 “OutPowr 0–10”

0–10 V

0 V = 0 kW

200 % Potencia nominal del variador

0–10 V

4 “TstData 0–10”

0–10 V

0 V = 0000

65535 (Hex FFFF)

0–10 V

5 “OutFreq 0–20”

0–20 mA

0 mA = 0 Hz

P035 [Maximum Freq]

0–20 mA

6 “OutCurr 0–20”

0–20 mA

0 mA = 0 Amps

200 % Amp carga plena del variador

0–20 mA

7 “OutVolt 0–20”

0–20 mA

0 mA = 0 Volts

120 % Volts salida nominal del variador 0–20 mA

8 “OutPowr 0–20”

0–20 mA

0 mA = 0 kW

200 % Potencia nominal del variador

0–20 mA

9 “TstData 0–20”

0–20 mA

0 mA = 0000

65535 (Hex FFFF)

0–20 mA

10 “OutFreq 4–20”

4–20 mA

4 mA = 0 Hz

P035 [Maximum Freq]

0–20 mA

11 “OutCurr 4–20”

4–20 mA

4 mA = 0 Amps

200 % Amp carga plena del variador

0–20 mA

12 “OutVolt 4–20”

4–20 mA

4 mA = 0 Volts

120 % Volts salida nominal del variador 0–20 mA

13 “OutPowr 4–20” 4–20 mA

4 mA = 0 kW

200 % Potencia nominal del variador

0–20 mA

14 “TstData 4–20”

4–20 mA

4 mA = 0000

65535 (Hex FFFF)

0–20 mA

15 “OutTorq 0–10”

0–10 V

0 V = 0 Amps

200 % Amp carga plena del variador

0–10 V

16 “OutTorq 0–20”

0–20 mA

0 mA = 0 Amps

200 % Amp carga plena del variador

0–20 mA

17 “OutTorq 4–20”

4–20 mA

4 mA = 0 Amps

200 % Amp carga plena del variador

0–20 mA

18 “Setpnt 0–10”

0–10 V

0 V = 0 %

Ajust 100.0 % pto ajus

0–10 V

19 “Setpnt 0–20”

0–20 mA

0 mA = 0 %

Ajust 100.0 % pto ajus

0–20 mA

20 “Setpnt 4–20”

4–20 mA

4 mA = 0 %

Ajust 100.0 % pto ajus

0–20 mA

21 “MinFreq 0–10”

0–10 V

0 V = Frec. mín.

P035 [Maximum Freq]

0–10 V

22 “MinFreq 0–20”

0–20 mA

0 mA = Frec. mín.

P035 [Maximum Freq]

0–20 mA

23 “MinFreq 4–20”

4–20 mA

4 mA = Frec. mín.

P035 [Maximum Freq]

0–20 mA

Estado de entrada

de Ent Digital 1

(Terminal de

E/S 05)

Estado de entrada

de Ent Digital 2

(Terminal de

E/S 06)

Estado de entrada

de Ent Digital 3

(Terminal de

E/S 07)

Fuente de frecuencia

Parámetro de Acel/

Decel usado(2)

0

0

0

[Preset Freq 0]

[Accel Time 1] / [Decel Time 1]

1

0

0

[Preset Freq 1]

[Accel Time 1] / [Decel Time 1]

0

1

0

[Preset Freq 2]

[Accel Time 2] / [Decel Time 2]

1

1

0

[Preset Freq 3]

[Accel Time 2] / [Decel Time 2]

0

0

1

[Preset Freq 4]

[Accel Time 1] / [Decel Time 1]

1

0

1

[Preset Freq 5]

[Accel Time 1] / [Decel Time 1]

0

1

1

[Preset Freq 6]

[Accel Time 2] / [Decel Time 2]

1

1

1

[Preset Freq 7]

[Accel Time 2] / [Decel Time 2]

(2) Cuando una entrada digital se establece en “Accel. 2 & Decel. 2”, y la entrada está activa, la entrada anula los ajustes

indicados en esta tabla.

Consulte el documento PowerFlex 40 User Manual para más información sobre parámetros.