English-15 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 17

Advertising
background image

English-15

P037 [Stop Mode]

0/9

0 = “Ramp, CF”

(1)

1 = “Coast, CF”

(1)

2 = “DC Brake, CF”

(1)

3 = “DCBrkAuto,CF”

(1)

4 = “Ramp”

5 = “Coast”

6 = “DC Brake”

7 = “DC BrakeAuto”

8 = “Ramp+EM B,CF”

9 = “Ramp+EM Brk”

(1)

Stop input also clears active fault.

0

Active stop mode for all stop sources [e.g. keypad,

run forward (I/O Terminal 02), run reverse (I/O

Terminal 03), RS485 port] except as noted below.

Important: I/O Terminal 01 is always a coast to

stop input except when P036 [Start Source] is set

for “3-Wire” control. When in three wire control, I/O

Terminal 01 is controlled by P037 [Stop Mode].

P038 [Speed Reference]

0/7

0 = “Drive Pot”

1 = “InternalFreq”

2 = “0-10V Input”

3 = “4-20mA Input”

4 = “Preset Freq”

5 = “Comm Port”

6 = “Stp Logic”

7 = “Anlg In Mult”

0

1 (IP66, Type 4X)

Sets the source of the speed reference to the

drive.

Important: When A051 or A052 [Digital Inx Sel] is

set to option 2, 4, 5, 6, 13 or 14 and the digital

input is active, A051, A052, A053 or A054 will

override the speed reference commanded by this

parameter. Refer to Chapter 1 of the PowerFlex 40

User Manual for details.

P039 [Accel Time 1]

0.0/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of accel for all speed increases.

P040 [Decel Time 1]

0.1/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of decel for all speed decreases.

P041 [Reset To Defalts]

0/1

0 = “Ready/Idle”

1 = “Factory Rset”

0

Resets all parameter values to factory defaults.

P042 [Voltage Class]

2/3

2 = “Low Voltage” (480V)

3 = “High Voltage” (600V)

3

Sets the voltage class of 600V drives.

P043 [Motor OL Ret]

0/1

0 = “Disabled”

1 = “Enabled”

0

Enables/disables the Motor Overload Retention function.

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

See the PowerFlex 40 User Manual for more information on parameters.