Power wiring, English-6 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 8

Advertising
background image

English-6

Power Terminal Block

Power Terminal Block Specifications

Power Wiring

Power Wire Rating

Recommended Copper

Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/

RHW-2

Anixter OLF-7xxxxx,

Belden 29501-29507 or

equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F)

RHH/RHW-2

Anixter 7V-7xxxx-3G

Shawflex 2ACD/3ACD or

equivalent

Terminal

(1)

Description

R/L1, S/L2

1-Phase Input

R/L1, S/L2, T/L3 3-Phase Input
U/T1

To Motor U/T1

=

Switch any two motor

leads to change

forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

P2, P1

DC Bus Inductor Connection (C Frame drives only.)
The C Frame drive is shipped with a jumper between

Terminals P2 and P1. Remove this jumper only when a DC

Bus Inductor will be connected. Drive will not power up

without a jumper or inductor connected.

DC+, DC-

DC Bus Connection

BR+, BR-

Dynamic Brake Resistor Connection
Safety Ground - PE

(1)

Important: Terminal screws may become loose during shipment. Ensure that all

terminal screws are tightened to the recommended torque before applying power to

the drive.

Frame

Maximum Wire Size

(2)

Minimum Wire Size

(2)

Torque

B

5.3 mm

2

(10 AWG)

1.3 mm

2

(16 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

C

8.4 mm

2

(8 AWG)

1.3 mm

2

(16 AWG)

2.9-3.7 N-m (26-33 lb.-in.)

(2)

Maximum/minimum sizes that the terminal block will accept - these are not

recommendations.

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+ BR-

DC- DC+

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3 P2

P1

BR+ BR-

DC- DC+

B Frame

C Frame