Advanced group parameters, English-16 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 18

Advertising
background image

English-16

Advanced Group Parameters

No. Parameter

Min/Max

Display/Options

Default

A051

A052

A053

A054

[Digital In1 Sel]

I/O Terminal 05

[Digital In2 Sel]

I/O Terminal 06

[Digital In3 Sel]

I/O Terminal 07

[Digital In4 Sel]

I/O Terminal 08

0/27

0 = “Not Used”

1 = “Acc & Dec 2”

2 = “Jog”

3 = “Aux Fault”

4 = “Preset Freq”

5 = “Local”

(1)

6 = “Comm Port”

7 = “Clear Fault”

8 = “RampStop,CF”

9 = “CoastStop,CF”

10 = “DCInjStop,CF”

11 = “Jog Forward”

12 = “Jog Reverse”

13 = “10V In Ctrl”

14 = “20mA In Ctrl”

15 = “PID Disable”

16 = “MOP Up”

17 = “MOP Down”

18 = “Timer Start”

19 = “Counter In”

20 = “Reset Timer”

21 = “Reset Countr”

22 = “Rset Tim&Cnt”

23 = “Logic In1”

24 = “Logic In2”

25 = “Current Lmt2”

26 = “Anlg Invert”

27 = “EM Brk Rlse”

4

4

5

11

(1)

Important: Speed source for IP66, NEMA/

UL Type 4X rated drives comes from A069

[Internal Freq].

A055 [Relay Out Sel]

0/24

0 = “Ready/Fault”

1 = “At Frequency”

2 = “MotorRunning”

3 = “Reverse”

4 = “Motor Overld”

5 = “Ramp Reg”

6 = “Above Freq”

7 = “Above Cur”

8 = “Above DCVolt”

9 = “Retries Exst”

10 = “Above Anlg V”

11 = “Logic In 1”

12 = “Logic In 2”

13 = “Logic 1 & 2”

14 = “Logic 1 or 2”

15 = “StpLogic Out”

16 = “Timer Out”

17 = “Counter Out”

18 = “Above PF Ang”

19 = “Anlg In Loss”

20 = “ParamControl”

21 = “NonRec Fault”

22 = “EM Brk Cntrl”

23 = “Above Fcmd”

24 = “MsgControl” (for

FRN 6.01 and later)

0

A056 [Relay Out Level]

0.0/9999

0.1

0.0

A058

A061

[Opto Out1 Sel]

[Opto Out2 Sel]

0/24

See A055 for Options.

2

1

A059

A062

[Opto Out1 Level]

[Opto Out2 Level]

0.0/9999

0.1

0.0

A064 [Opto Out Logic]

0/3

1

0

A055, A058 & A061 Setting

A056, A059 & A062 Min/Max

6

0/400 Hz

7

0/180%

8

0/815 Volts

10

0/100%

16

0.1/9999 Secs

17

1/9999 Counts

18

1/180 degs

20

0/1

23

0/400 Hz

A064 Option

Opto Out1 Logic

Opto Out2 Logic

0

NO (Normally Open)

NO (Normally Open)

1

NC (Normally Closed)

NO (Normally Open)

2

NO (Normally Open)

NC (Normally Closed)

3

NC (Normally Closed)

NC (Normally Closed)

See the PowerFlex 40 User Manual for more information on parameters.