Installing the Adapter

2-5

Network with PowerFlex Drives at Starting and/or Ending Nodes

For a network with PowerFlex drives at the starting and/or ending nodes
(

Figure 2.3

), set their 20-COMM-B adapter’s TERM, -BIAS, and +BIAS

switches to the “Down” (On) position. All other PowerFlex drive
network nodes must have these switches set to the “Up” (Off) position.

Figure 2.3 Example Network with PowerFlex Drives at Starting and/or Ending Nodes

Network with PowerFlex Drives at Other Nodes

For a network with PowerFlex drives at other node locations — not
starting and/or ending nodes (

Figure 2.4

), set the TERM, -BIAS, and

+BIAS switches to the “Up” (Off) position. In this network scenario,
other brands of building automation products at the starting and/or
ending nodes require appropriate termination and bias resistors. Refer to
their instruction documentation for details.

Figure 2.4 Example Network with PowerFlex Drives at Other Nodes

BACnet MS/TP Network

Node 1

(Starting Node)

Node

n

(Ending Node)

Node 2

Node 3

Node 4

"Down" (On) Positions

"Up" (Off) Positions

20-COMM-B Adapter Settings for

TERM, -BIAS, and +BIAS Switches

"Down" (On) Positions

■ ■ ■

BACnet MS/TP Network

Node 1

(Starting Node)

PowerFlex 7-Class Drives

Other Brand

Building Automation

Product

Node

n

(Ending Node)

"Up" (Off) Positions

Node 2

Node 3

Node 4

Requires

Termination and

Bias Resistors

■ ■ ■

Other Brand

Building Automation

Product

Requires

Termination and

Bias Resistors

20-COMM-B Settings

for TERM, -BIAS, and

+BIAS Switches