Adapter Parameters

B-3

07

[Baud Rate Act]
Displays the baud rate (kilobits per second)
actually used by the adapter.

Default:

0 = Unknown

Values:

0 = Unknown
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps

Type:

Read Only

08

[MAC Address]
Displays the actual address selected by the MAC
Address Switches SW1-SW7 (

Figure 2.1

) on the

adapter. This value is latched when the adapter
powers up.

Default:

0

Minimum:

0

Maximum:

127

Type:

Read Only

09

[Max Master]
Sets the maximum MAC Address for any device in
the BACnet MS/TP token ring.

Default:

127

Minimum:

0

Maximum:

127

Type:

Read/Write

Reset Required:

Yes

10

[Max Info Frames]
Sets the maximum number of messages that the
adapter can transmit while it owns the token.

Default:

1

Minimum:

1

Maximum:

255

Type:

Read/Write

Reset Required:

Yes

11

[Device Instance]
Sets the Device Instance Number used by the
adapter.

Default:

160000

Minimum:

0

Maximum:

4194302

Type:

Read/Write

Reset Required:

Yes

Parameter
No. Name and Description

Details