Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual
Page 55

Adapter Parameters
B-3
07
[Baud Rate Act]
Displays the baud rate (kilobits per second)
actually used by the adapter.
Default:
0 = Unknown
Values:
0 = Unknown
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps
Type:
Read Only
08
[MAC Address]
Displays the actual address selected by the MAC
Address Switches SW1-SW7 (
) on the
adapter. This value is latched when the adapter
powers up.
Default:
0
Minimum:
0
Maximum:
127
Type:
Read Only
09
[Max Master]
Sets the maximum MAC Address for any device in
the BACnet MS/TP token ring.
Default:
127
Minimum:
0
Maximum:
127
Type:
Read/Write
Reset Required:
Yes
10
[Max Info Frames]
Sets the maximum number of messages that the
adapter can transmit while it owns the token.
Default:
1
Minimum:
1
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
11
[Device Instance]
Sets the Device Instance Number used by the
adapter.
Default:
160000
Minimum:
0
Maximum:
4194302
Type:
Read/Write
Reset Required:
Yes
Parameter
No. Name and Description
Details