Port status indicator, Port status indicator -2 – Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual

Page 44

Advertising
background image

5-2

Troubleshooting

PORT Status Indicator

State

Cause

Corrective Actions

Off

The adapter is not powered or
is not properly connected to
the drive.

• Securely connect the adapter to the drive

using the Internal Interface (ribbon)
cable.

• Apply power to the drive (or adapter if

mounted in a DPI External Comms Kit).

Flashing
Red

The adapter is not receiving a
ping message from the drive.

• Verify that cables are securely connected

and not damaged. Replace cables if
necessary.

• Cycle power to the drive (or adapter if

mounted in a DPI External Comms Kit).

Solid Red

The drive has refused an I/O
connection from the adapter.
Another DPI peripheral is
using the same DPI port as
the adapter.

Important: Cycle power to the drive (or
adapter if mounted in a DPI External
Comms Kit) after making the following
correction:

• Verify that all DPI cables on the drive are

securely connected and not damaged.
Replace cables if necessary.

Orange

The adapter is connected to a
product that does not support
Rockwell Automation DPI
communications.

Connect the adapter to a product that
supports Allen-Bradley DPI
communications (for example, a PowerFlex
70 or PowerFlex 700 drive).

Flashing
Green

The adapter is establishing an
I/O connection to the drive.

No action required.

Solid Green The adapter is properly

connected and is
communicating with the drive.

No action required.