Viewing and clearing adapter diagnostic items, To view and clear adapter diagnostic items, Viewing and clearing adapter diagnostic items -5 – Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual

Page 47

Advertising
background image

Troubleshooting

5-5

The following adapter diagnostic items can be viewed using
DriveExplorer (version 3.01 or higher) or DriveExecutive (version 3.01
or higher) software, or an LCD PowerFlex HIM (Diagnostic/Device
Items).

To view and clear adapter diagnostic items

Viewing and Clearing Adapter Diagnostic Items

Step

Keys

Example Screen

Viewing Diagnostic Items

1. Access parameters in the adapter.

Refer to

Using the PowerFlex

7-Class HIM on page 3-2

.

2. Press the Up Arrow or Down Arrow

to scroll to Diagnostics.

3. Press Enter to display the

Diagnostics menu in the adapter.

4. Repeat steps 2 and 3 to enter the

Device Items option.

5. Press the Up Arrow or Down Arrow

to scroll through the items.

Clearing Diagnostic Items

1. Access parameters in the Adapter.

Refer to

Using the PowerFlex

7-Class HIM on page 3-2

.

2. Press the Up Arrow or Down Arrow

to scroll to Parameter.

3. Press Enter to display the list of

parameters in the adapter.

4. Repeat steps 2 and 3 to select

Parameter 28 - [Clear Counters].

5. Set the value to 1 = Clear and then

press Enter to clear the following
diagnostic items: 24, 25, 26, 27, and
28.

OR

OR

OR

Main Menu:

Diagnostics

Parameter
Device Select

Device Item #

13

MAC Addr SW

1

Parameter #: 28
Clear Counters

1

Clear

Main Menu:
Diagnostics

Parameter

Device Select

Advertising