Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual

Page 27

Advertising
background image

Installing the Adapter

2-11

Figure 2.8 Typical Network Terminal Connections

5. Insert the 3-pin linear plug into the mating adapter socket.

6. Install or close the drive cover.

7. Apply power to the drive.

8. Verify that adapter Parameter 07 - [Baud Rate Act] is reporting the

actual network baud rate. If not, use Parameter 06 - [Baud Rate
Cfg]
to set the adapter to a fixed baud rate that matches the network
baud rate.

Node 1

Node 2

Node "n"

SHLD +B

-A

SHLD +B

-A

SHLD +B

-A

Terminal

Signal

Function

SHLD Termination Shield

Termination

+B

Signal B

TxRxD+

-A

Signal A

TxRxD-

TIP: After the drive is connected and communicating on the BACnet
MS/TP network, it may be necessary to set additional adapter parameters
to meet your application requirements. For example:

Parameter 02 - [Comm Loss Action]

Parameter 03 - [Comm Loss Time]

To access adapter parameters when using the LCD HIM, navigate to the
Device Select screen. Then select the BACnet adapter (20-COMM-B)
and press the Enter function key.

For adapter parameter configuration details, please refer to

Chapter 3

.