Appendix B provides information about the BACnet MS/TP adapter
parameters.

The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.

Topic

Page

About Parameter Numbers

B-1

Parameter List

B-1

About Parameter Numbers

Configuration Tool

Numbering Scheme

• DriveExplorer

• DriveExecutive

• HIM

The adapter parameters begin with parameter 1. For
example, Parameter 01 - [Reset Module] is parameter
1 as indicated by this manual.

Parameter List

Parameter
No. Name and Description

Details

01

[Reset Module]
No action if set to “Ready.” Resets the adapter if
set to “Reset Module.” Restores the adapter to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.

Default:

0 = Ready

Values

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:

No

!

ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.