Verifying/setting key adapter parameters – Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual

Page 25

Advertising
background image

Installing the Adapter

2-9

Table 2.B Drive and Adapter Start-Up Status Indications

Verifying/Setting Key Adapter Parameters

To access adapter parameters when using the LCD HIM, navigate to the
Device Select screen. Then select the BACnet communications adapter
(20-COMM-B) and press the Enter function key.

1. Verify that adapter Parameter 08 - [MAC Address] is reporting the

MAC address set in

Setting the MAC Address on page 2-2

.

2. Set adapter Parameter 11 - [Device Instance] to a unique number

for representation to the Building Automation Controller. For more
information, see

Setting the Device Instance Number on page 3-3

.

3. Reset the adapter by setting adapter Parameter 01 - [Reset Module]

to “1” (Reset Module) so that the new Device Instance Number takes
effect.

Item Name

Color

State

Description

Drive STS Indicator

STS
(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing,
Drive Stopped

An inhibit condition exists – the drive cannot be started.
Check drive Parameter 214 - [Start Inhibits].

Flashing,
Drive Running

An intermittent type 1 alarm condition is occurring. Check
drive Parameter 211 - [Drive Alarm 1].

Steady,
Drive Running

A continuous type 1 alarm condition exists. Check drive
Parameter 211 - [Drive Alarm 1].

Red

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Adapter Status Indicators

PORT

Green

Flashing

Normal Operation. The adapter is establishing an I/O
connection to the drive. It will turn solid green or red.

Steady

Normal Operation. The adapter is properly connected and
communicating with the drive

MOD

Green

Flashing

Normal Operation. The adapter is operating but is not
transferring I/O data.

Steady

Normal Operation. The adapter is operating and
transmitting I/O data.

NET A

Green

Flashing

Normal Operation. The adapter is properly connected and
communicating on the network.

NET B

Green

Off

Normal Operation. The adapter is properly connected but
is idle.

Flashing

Normal Operation. The adapter is transmitting data.

Advertising