Troubleshooting

5-3

MOD Status Indicator

State

Cause

Corrective Actions

Off

The adapter is not powered or
is not properly connected to
the drive.

• Securely connect the adapter to the drive

using the Internal Interface (ribbon)
cable.

• Apply power to the drive (or adapter if

mounted in a DPI External Comms Kit).

Flashing
Red

The adapter has failed the
firmware test.

• Cycle power to the drive (or adapter if

mounted in a DPI External Comms Kit).

• If cycling power does not correct the

problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.

• If resetting defaults does not correct the

problem, flash the adapter with the latest
firmware release.

Flashing
Green

The adapter is operational, but
is not transferring I/O data.

Enable the network device that is providing
control to the adapter.

Solid Green The adapter is operational and

transferring I/O data.

No action required.