5-8

Troubleshooting

Events

Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:

Code Event Description
1

No Event

Empty event queue entry.

2

DPI Bus Off Flt

A bus-off condition was detected on DPI. This event may be caused by
loose or broken cables or by noise.

3

Ping Time Flt

A ping message was not received on DPI within the specified time.

4

Port ID Flt

The adapter is not connected to a correct port on a DPI product.

5

Port Change Flt

The DPI port changed after start up.

6

Host Sent Reset

The drive sent a reset event message.

7

EEPROM Sum Flt

The EEPROM in the adapter is corrupt.

8

Online @ 125 kbps The adapter detected the drive communicating at 125 kbps.

9

Online @ 500 kbps The adapter detected the drive communicating at 500 kbps.

10

Bad Host Flt

The adapter was connected to an incompatible product.

11

Dup Port Flt

Another peripheral with the same port number is already in use.

12

Type 0 Login

The adapter has logged in for Type 0 control.

13

Type 0 Time Flt

The adapter has not received a Type 0 status message within the
specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt

The drive rejected an attempt to log in to a Datalink because the Datalink
is not supported or is used by another peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the specified time.

17

Reserved

18

Control Disabled

The adapter has sent a “Soft Control Disable” command to the drive.

19

Control Enabled

The adapter has sent a “Soft Control Enable” command to the drive.

20

Message Timeout

A client-server message sent by the adapter was not completed within 1 sec.

21

Fault Cfg Error

One of the Flt Cfg XX In parameters is set to a value greater than 65535
and the drive requires a 16-bit value.

22

App Updated

New application firmware was detected.

23

Net Comm Flt

The adapter detected a communications fault on the network.

24

Net Sent Reset

The adapter received a fault from the network.

25

Net Close Flt

An I/O connection from the network to the adapter was closed.

26

Net Idle Flt

The adapter is receiving “idle” packets from the network.

27

Net Open

An I/O connection from the network to the adapter has been opened.

28

Net TImeout Flt

An I/O connection from the network to the adapter has timed out.

29

PCCC IO Close

The device sending PCCC Control messages to the adapter has set the
PCCC Control Timeout to zero.

30

PCCC IO Open

The adapter has begun receiving PCCC Control messages.

31

PCCC IO Time Flt

The adapter has not received a PCCC Control message for longer than
the PCCC Control Timeout.

32

Watchdog T/O Flt

The software detects a failure.

33

EEPROM Init

A blank EEPROM map revision was detected.

34

Normal Startup

The adapter successfully started up.

35

Manual Reset

The adapter was reset by changing its Reset Module parameter.