Configuring the Adapter

3-7

The value of Parameter 06 - [Baud Rate Cfg] determines the baud rate
used by the adapter. The Autobaud setting will detect the baud rate used
on the network if another device is setting the baud rate. Your application
may require a different setting.

1. Set the value of Parameter 06 - [Baud Rate Cfg] to the baud rate at

which your network is operating.

Figure 3.5 Baud Rate Screen on PowerFlex 4-Class HIM (22-HIM-*)

2. Reset the adapter (see

Resetting the Adapter

) so that the new baud

rate takes effect.

Changes to switch settings or some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by cycling power to the drive or by using Parameter 01 - [Reset
Module]
.

Set Parameter 01 - [Reset Module] to Reset Module.

Figure 3.6 Reset Screen on an LCD HIM

Setting the Baud Rate

Value

Description

0

Autobaud (Default)

1

9600

2

19200

3

38400

4

76800

Port 5 Device

20-COMM-B

Parameter #: 06
Baud Rate Cfg

0

Autobaud

Resetting the Adapter

!

ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault when
you reset the adapter. Determine how your drive will respond before
resetting a connected adapter.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Port 5 Device

20-COMM-B

Parameter #: 01
Reset Module

1

Reset Module

Advertising