Enhanced Program Group
(continued)
E220 [Ki Speed Loop]
Sets the I-Gain used in the PI calculation of the speed loop.
Values
Default:
2.0
Min/Max:
0.0/400.0
Display:
0.1
E221 [Kp Speed Loop]
Sets the P-Gain used in the PI calculation of the speed loop.
Values
Default:
0.5
Min/Max:
0.0/200.0
Display:
0.1
E222 [Positioning Mode]
Stop drive before changing this parameter.
Defines the positioning transition mode used for the position steps. For additional information refer to
Values
Default:
0
Min/Max:
0/4
Display:
1
E222 Option
Transition Mode
Description
0
1
2
3
4
Time Steps
Preset Input
Step Logic
Preset StpL
StpLogic-Lst
Steps based on time.
Preset inputs directly command a given step.
Use Step Logic commands. Always start from Step 0.
Use Preset inputs to determine starting step then Step Logic commands.
Use Step Logic commands from last StepLogic step at last drive stop.
E223 [Find Home Freq]
Sets the maximum frequency the drive uses when “Find Home” is issued. For additional information
refer to
Values
Default:
10.0 Hz
Min/Max:
0.1/500.0 Hz
Display:
0.1 Hz