Writing (06) logic command data, Writing (06) logic command data. . . . . . c-4, Velocity bit definitions – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 152: C-4 rs485 (dsi) protocol

C-4
RS485 (DSI) Protocol
Writing (06) Logic Command Data
The PowerFlex 40P drive can be controlled via the network by sending
Function Code 06 writes to register address 8192 (Logic Command).
[Start Source] must be set to 5 “Comm Port” in order to accept the
commands. Parameter
[Cmd Stat Select] is used to select Velocity
or Position Bit definitions.
Velocity Bit Definitions
Logic Command - E249 = 0 “Velocity”
Address (Decimal)
Bit(s)
Description
8192
0
1 = Stop, 0 = Not Stop
1
1 = Start, 0 = Not Start
2
1 = Jog, 0 = No Jog
3
1 = Clear Faults, 0 = Not Clear Faults
5,4
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command
6
1 = Logic In 1
7
1 = Logic In 2
9,8
00 = No Command
01 = Accel Rate 1
10 = Accel Rate 2
11 = Hold Accel Rate Selected
11,10
00 = No Command
01 = Decel Rate 1
10 = Decel Rate 2
11 = Hold Decel Rate Selected
14,13,12
000 = No Command
001 = Freq. Source = P036 [Start Source]
010 = Freq. Source = A069 [Internal Freq]
011 = Freq. Source = Comms (Addr 8193)
100 = A070 [Preset Freq 0]
101 = A071 [Preset Freq 1]
110 = A072 [Preset Freq 2]
111 = A073 [Preset Freq 3]
15
Not Used