Programming and Parameters
Advanced Display Group
d301 [Drive Status 2]
Present operating condition of the drive.
When in Positioning mode, Bit 10 indicates positive or negative position in relation to Home.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Dir Positive
Bit 0
At Position
Bit 1
At Home
Bit 2
Drive Homed
Bit 3
d302 [Fibers Status]
Present status of the Fibers features.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Sync Hold
Digit 1
Sync Ramp
Digit 2
Traverse On
Digit 3
Traverse Dec
Digit 4
d303 [Slip Hz Meter]
Displays the current amount of slip being applied to the motor frequency.
Values
Default:
Read Only
Min/Max:
0.0/25.0 Hz
Display:
0.1 Hz
d304 [Speed Feedback]
32 bit parameter.
Displays the value of the actual motor speed (whole number portion) whether measured by encoder/
pulse train feedback or estimated.
Values
Default:
Read Only
Min/Max:
0/64000 RPM
Display:
1 RPM