Velocity StepLogic™, Basic Logic and Timer/Counter Functions
Velocity StepLogic Using Timed Steps
To activate this function, set parameter
[Speed Reference] to 6 “Stp
Logic”. Three parameters are used to configure the logic, speed
reference and time for each step.
•
Logic is defined using parameters
[Stp Logic x].
•
Preset Speeds are set with parameters
[Preset Freq x].
•
Time of operation for each step is set with parameters
[Stp Logic Time x].
The direction of motor rotation can be forward or reverse.
Figure E.1 Using Timed Steps
Velocity StepLogic Sequence
•
Sequence begins with a valid start command.
•
A normal sequence begins with Step 0 and transition to the next step
when the corresponding StepLogic time has expired.
•
Step 7 is followed by Step 0
•
Sequence repeats until a stop is issued or a fault condition occurs.
Time
0
Forward
Reverse
Step 0
Step 1
Step 2
Step 3 Step 4 Step 5 Step 6
Step 7