Counter function – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 166

E-6
Velocity StepLogic™, Basic Logic and Timer/Counter Functions
Counter Function
Digital inputs and outputs control the counter function and are
configured with parameters
[Digital Inx Sel] set to 19
“Counter In” and 21 “Reset Countr”.
Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level parameters
[Relay Out Level],
[Opto Out1 Level] and
[Opto Out2 Level] are used to set the
desired count value.
Parameters
[Relay Out Sel],
[Opto Out2 Sel] are set to 17 “Counter Out” which causes the output to
change state when the level is reached.
Example
•
A photo eye is used to count packages on a conveyor line.
•
An accumulator holds the packages until 5 are collected.
•
A diverter arm redirects the group of 5 packages to a bundling area.
•
The diverter arm returns to its original position and triggers a limit
switch that resets the counter.
•
Parameters are set to the following options:
–
[Digital In1 Sel] set to 19 to select “Counter In”
–
[Digital In2 Sel] set to 21 to select “Reset Countr”
–
[Relay Out Sel] set to 17 to select “Counter Out”
–
[Relay Out Level] set to 5.0 (Counts)