Advanced program group, Continued), A119 [skip frequency – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 84: A120 [skip freq band, A121 [stall fault time

3-38
Programming and Parameters
Advanced Program Group
(continued)
A119 [Skip Frequency]
Related Parameter(s):
Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.
Values
Default:
0 Hz
Min/Max:
0/500 Hz
Display:
1 Hz
A120 [Skip Freq Band]
Related Parameter(s):
Determines the bandwidth around
[Skip Frequency]. A120 [Skip Frequency Band] is split
applying 1/2 above and 1/2 below the actual skip frequency.
A setting of 0.0 disables this parameter.
Values
Default:
0.0 Hz
Min/Max:
0.0/30.0 Hz
Display:
0.1 Hz
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
A121 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options
0 “60 Seconds” (Default)
1 “120 Seconds”
2 “240 Seconds”
3 “360 Seconds”
4 “480 Seconds”
5 “Flt Disabled”