A103, A105, Advanced program group – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 80: Continued), A103 [comm data rate, A104 [comm node addr, A105 [comm loss action, A106 [comm loss time

3-34
Programming and Parameters
Advanced Program Group
(continued)
A103 [Comm Data Rate]
Related Parameter(s):
Sets the serial port rate for the RS485 (DSI) port.
Important: Power to drive must be cycled before any changes will affect drive operation.
Options
0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4 “19.2K”
5 “38.4K”
A104 [Comm Node Addr]
Related Parameter(s):
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important: Power to drive must be cycled before any changes will affect drive operation.
Values
Default:
100
Min/Max:
1/247
Display:
1
A105 [Comm Loss Action]
Selects the drive’s response to a loss of the communication connection or excessive communication
errors.
Options
0 “Fault” (Default)
Drive will fault on an
Comm Loss and coast to stop.
1 “Coast Stop”
Stops drive via coast to stop.
2 “Stop”
Stops drive via
[Stop Mode] setting.
3 “Continu Last”
Drive continues operating at communication commanded
speed saved in RAM.
A106 [Comm Loss Time]
Related Parameter(s):
Sets the time that the drive will remain in communication loss before implementing the option selected
in
Values
Default:
5.0 Secs
Min/Max:
0.1/60.0 Secs
Display:
0.1 Secs