3-34

Programming and Parameters

Advanced Program Group

(continued)

A103 [Comm Data Rate]

Related Parameter(s):

b015

Sets the serial port rate for the RS485 (DSI) port.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “1200”

1 “2400”

2 “4800”

3 “9600” (Default)

4 “19.2K”

5 “38.4K”

A104 [Comm Node Addr]

Related Parameter(s):

b015

Sets the drive node address for the RS485 (DSI) port if using a network connection.

Important: Power to drive must be cycled before any changes will affect drive operation.

Values

Default:

100

Min/Max:

1/247

Display:

1

A105 [Comm Loss Action]

Related Parameter(s):

b015

,

P037

,

A106

Selects the drive’s response to a loss of the communication connection or excessive communication
errors.

Options

0 “Fault” (Default)

Drive will fault on an

F81

Comm Loss and coast to stop.

1 “Coast Stop”

Stops drive via coast to stop.

2 “Stop”

Stops drive via

P037

[Stop Mode] setting.

3 “Continu Last”

Drive continues operating at communication commanded
speed saved in RAM.

A106 [Comm Loss Time]

Related Parameter(s):

b015

,

A105

Sets the time that the drive will remain in communication loss before implementing the option selected
in

A105

[Comm Loss Action].

Values

Default:

5.0 Secs

Min/Max:

0.1/60.0 Secs

Display:

0.1 Secs