Programming and Parameters
3-33
Advanced Program Group
(continued)
A098 [SW Current Trip]
Related Parameter(s):
Enables/disables a software instantaneous (within 100 ms) current trip.
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps
A099 [Process Factor]
Related Parameter(s):
Scales the output frequency value displayed by
[Process Display].
Values
Default:
30.0
Min/Max:
0.1/999.9
Display:
0.1
Output
Freq
Process
Factor
Process
Display
=
x
A100 [Fault Clear]
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer”
(Parameters
-
[Fault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel with a 4-digit password.
Options
0 “Unlocked” (Default)
1 “Locked”
A102 [Testpoint Sel]
Related Parameter(s):
Used by Rockwell Automation field service personnel.
Values
Default:
400
Min/Max:
400/FFFF
Display:
1 Hex