Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 119

Troubleshooting
4-5
F91
Encoder Loss
Requires differential encoder.
One of the 2 encoder channel
signals is missing.
1. Check Wiring.
2. If P038 [Speed Reference] = 9
“Positioning” and E216 [Motor
Fdbk Type] = 5 “Quad Check”
swap the Encoder channel inputs
(see
) or swap any two
motor leads.
3. Replace encoder.
F100 Parameter
Checksum
➁
The checksum read from the
board does not match the
checksum calculated.
Set
[Reset To Defalts] to
option 1 “Reset Defaults”.
F111 Enable
Hardware
DriveGuard Safe-Off Option
(Series B) board is installed and
the ENBL enable jumper has not
been removed.
1. Remove the ENBL enable
jumper.
2. Cycle power.
DriveGuard Safe-Off Option
(Series B) board has failed.
1. Remove power to the drive.
2. Replace DriveGuard Safe-Off
Option (Series B) board.
Hardware Enable circuitry has
failed.
Replace drive.
F122 I/O Board Fail
➁
Failure has been detected in the
drive control and I/O section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
(1)
for a description of fault types.
No.
Fault
Ty
p
e
(1
)
Description
Action