P039, P040, Basic program group – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 59: Continued), P039 [accel time 1, P040 [decel time 1, P041 [reset to defalts, Programming and parameters 3-13

Programming and Parameters
3-13
Basic Program Group
(continued)
P039 [Accel Time 1]
Related Parameter(s):
-
Sets the rate of acceleration for all speed increases.
Values
Default:
10.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
P040 [Decel Time 1]
Related Parameter(s):
-
Sets the rate of deceleration for all speed decreases.
Values
Default:
10.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
P041 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options
0 “Ready/Idle” (Default)
1 “Factory Rset”
•
After the reset function is complete, this parameter will set
itself back to “0”.
•
fault.