Basic display group, Continued), B018 [elapsed run time – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 53: B019 [testpoint data, B022 [output power, B023 [output powr fctr

Programming and Parameters
3-7
Basic Display Group
(continued)
b018 [Elapsed Run Time]
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
Values
Default:
Read Only
Min/Max:
0/9999 Hrs
Display:
1 = 10 Hrs
b019 [Testpoint Data]
Related Parameter(s):
The present value of the function selected in
[Testpoint Sel].
Values
Default:
Read Only
Min/Max:
0/FFFF
Display:
1 Hex
b020 [Analog In 0-10V]
Related Parameter(s):
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
Values
Default:
Read Only
Min/Max:
0.0/100.0%
Display:
0.1%
b021 [Analog In 4-20mA]
Related Parameter(s):
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
Values
Default:
Read Only
Min/Max:
0.0/100.0%
Display:
0.1%
b022 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.00/(Drive Rated Power
×
2)
Display:
0.01 kW
b023 [Output Powr Fctr]
The angle in electrical degrees between motor voltage and motor current.
Values
Default:
Read Only
Min/Max:
0.0/180.0 deg
Display:
0.1 deg