Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 21

Advertising
background image

Installation/Wiring

1-9

2.15

10.32

13.47

9.56

8.80

2.92

25.90

4.12

1.15

4.63

Ø.453 (4)-PL. See Note 1

1.56

17.50

32.16

6.60

9.50

1.78

0.44

0.44

2.96

2.96

FIELD CONTROL WIRING

Wire Size Strip Length

Name

Reference

[N-M]

[IN-LBF]

[AWG]

[Inch]

A33

#6-32 Screw

0.90

8

24 to 10

Screwdriver Blade:
0.032" Thk. x 0.125" Wide
Screwdriver Blade:
0.017" Thk. x 0.094" Wide

0.79

7

26 to 12

0.31

0.22

1.9

28 to 16

0.25

A1-P1 LINE SYNC. ASS'Y HARNESS CONNECTOR

A1-P1
MATE

Cooling Fan Requires 1.13" Minimum
Unobstructed Space Below Fan

DC

Neg (-)

DC

Pos (+)

DC Bus Measurement

Points on Laminated

Bus Ass'y 0.25" x 0.032"
Male Faston. Accessible

by Removal of Top Cover.

AIRFLOW

SEE DETAIL
GATE KILL

A22-TB1 & TB2

Main Control Ass'y

Terminal Blocks

A11-P2 Voltage

Feedback

Resistor Ass'y

Terminal

Block 7-Pos.

A12-P1 Active

Converter Control

Ass'y Terminal

Block 15-Pos.

BOTTOM VIEW

RIGHT SIDE VIEW

SEE DETAIL COG

DETAIL COG

IN

OUT

Y

X

2 1

DETAIL GATE KILL

SCALE 5:8

A32

A31

A33

A33

Torque

A12-P1
A11-P2
A22-TB1
A22-TB2

Pin Housing, AMP P/N 172171-1

Socket Housing, AMP P/N 172163-1

Socket, AMP P/N 770903-3
Pin, AMP P/N 770904-3

A33 Gate Kill
2-Pos. Terminal Block
With #6-32 Phillips/Slotted
Screws. Accepts #6 Stud Size
Spade Tongue Terminal.
Max. Width is 0.37".

8.27 (A33)

6.17 (A22-TB1 & TB2)

5.54 (DC Bus Measurement Points)

CENTER OF GRAVITY:
X = 17.5"
Y = 3.1"
Z = 7.4" (into Plane
of Drawing)
WEIGHT:
162 LBS.

SCALE 5:16

Advertising