Installing input power wiring, Installing input power wiring -17 – Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 29

Advertising
background image

Installation/Wiring

1-17

Installing Input Power
Wiring

This section describes incoming line components and how to install them.

Installing Transformers and Reactors (Not Recommended)

The LPM20 AC drive may be used on distribution systems with 100,000
amps or less symmetrical fault current capacity. The Drive Input
components consists of a 3% line reactor and a harmonic line filter.
Additional input inductance is not recommended.

Figure 1.8 Drive Input Wiring

NOTE: Proper torque for Line Side Lugs is labeled on the circuit breaker.

L1

L2

L3

Circuit Breaker
Line Side Lugs

Ground Lug
2-600 MCM

Torque Label for

Line Side Lugs

Advertising