Corrosion inhibitor, Biocide – Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 28

Advertising
background image

1-16

Installation/Wiring

Table 1.C Coolant Requirements for LPM20 Drives

Corrosion Inhibitor

A corrosion inhibitor is required. The following two options are approved
sources:

1. Chemtool, Inc. (www.chemtool.com) part number Watertool 4435-C.

The recommended concentration of the inhibitor is 8 to 10% by volume.

2. Dow Chemical (www.dow.com) Dowtherm

®

SR-1 inhibited ethylene

glycol. The recommended concentration of the inhibitor is 25% by
volume.

Dowtherm is a registered trademark of the Dow Chemical Company.

Biocide

A biocide may be needed to control biological growth. Use of a biocide is
permitted. For specific recommendations, consult a reputable water
treatment company.

LPM20 Drive
Catalog Number
(positions 1-7 only)

Max. Output
Current (Amps)

Coolant
Temperature
Range (°C)

Minimum
Coolant Flowrate
(GPM)

Pressure Drop From Drive
Inlet to Drive Outlet (PSIG) at
Minimum Coolant Flow Rate

Coolant
Type

20ND608

608

5 to 40

7

10

Water

(1)

608

0 to 40

7

10

WEG25

(2)

550

0 to 40

7

10

WEG50

(3)

608

0 to 40

10

22

WEG50

(3)

608

0 to 30

7

10

WEG50

(3)

(1)

Water equals good quality or distilled water with Chemtool, Inc. corrosion inhibitor, 2% inhibitor by volume.

(2)

WEG25 equals good quality or distilled water with approved ethylene glycol, 25% glycol by volume.

(3)

WEG50 equals good quality or distilled water with approved ethylene glycol, 50% glycol by volume.

!

ATTENTION: Ethylene glycol must be inhibited and silicate
free. Use of common silicate-containing, automotive-type
ethylene glycol solutions is prohibited as they may damage the
drive and cooling module equipment.

Advertising