Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 40

Advertising
background image

1-28

Installation/Wiring

Table 1.J TB2 Terminals

Terminal

Signal

Description

Related
Parameter

1

24V dc Common (-)

Drive supplied 24V dc logic input power
Rating: 300 mA maximum load

2

24V dc Source (+)

3

Digital Output 1

24V dc Open Collector (sinking logic)
Rating: Internal Source = 150 mA maximum
External Source = 750 mA

816, 847

4

Digital Output 1/2 Common

Common for Digital Outputs 1 and 2

5

Digital Output 2

24V dc Open Collector (sinking logic)
Rating: Internal Source = 150 mA maximum
External Source = 750 mA

851, 852

6

Relay Output 3 (NC)

Relay contact output
Rating: 115V ac or 24V dc = 2 A maximum Inductive/Resistive

856, 857

7

Relay Output 3 Common

8

Relay Output 3 (NO)

9

Digital Input 1-3 Common

Common for Digital Inputs 1, 2, and 3

10

Digital Input 1

High speed 12-24V dc sourcing Digital Input
Load: 15 mA at 24V dc

825

11

Digital Input 2

826

12

Digital Input 3

Load: 15 mA at 24V dc sourcing

827

13

Digital Input 4-6 Common

Common for Digital Inputs 4, 5, and 6

14

Digital Input 4

Load: 10 mA at 24V dc sinking/sourcing
Load: 7.5 mA at 115V ac

828

15

Digital Input 5

829

16

Digital Input 6 (HW Enable)

830

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

Advertising