Troubleshooting

3-5

Motor and/or drive will not accelerate to Commanded Speed.

Motor operation is unstable.

Drive will not reverse motor direction.

Cause(s)

Indication

Corrective Action

Acceleration time is excessive.

None

Reprogram [Accel Time x] parameter.

Excess load or short acceleration
times force the drive into current
limit, slowing or stopping
acceleration.

None

1. Check [Drive Status 2] parameter, bit 10 to

see if the drive is in Current Limit.

2. Remove excess load or reprogram [Accel

Time x] parameter.

Speed command source or value is
not as expected.

None

Check for the proper Speed Command using
Steps 1 through 7 previously described.

Programming is preventing the drive
output from exceeding limiting
values.

None

Check [Maximum Speed] parameter and
[Maximum Freq] parameter to assure that
speed is not limited by programming.

Cause(s)

Indication

Corrective Action

Motor data was incorrectly entered. None

Correctly enter motor nameplate data.

Cause(s)

Indication

Corrective Action

Digital input is not selected for
reversing control.

None

Check [Digital Inx Sel] parameter. Choose
correct input and program for reversing mode.

Digital input is incorrectly wired.

None

Check input wiring.

(See page 1-25)

Direction mode parameter is
incorrectly programmed.

None

Reprogram [Direction Mode] parameter for
analog “Bipolar” or digital “Unipolar” control.

Motor wiring is improperly phased
for reverse.

None

Switch two motor leads.

A bipolar analog speed command
input is incorrectly wired or signal is
absent.

None

1. Use meter to check that an analog input

voltage is present.

2. Check wiring.

(See page 1-25)

Positive voltage commands forward direction.
Negative voltage commands reverse direction.