Logic command word – Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 66

Advertising
background image

A-4

Supplemental Drive Information

Logic Command Word

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description

x Normal

Stop

0 = Not Normal Stop
1 = Normal Stop

x

Start

(1)

(1)

A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start
condition will start the drive.

0 = Not Start
1 = Start

x

Jog 1

0 = Not Jog using [Jog Speed 1]
1 = Jog using [Jog Speed 1]

x

Clear
Fault

(2)

(2)

To perform this command, the value must switch from “0” to “1.”

0 = Not Clear Fault
1 = Clear Fault

x x

Unipolar
Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control

x

Reserved

x

Jog 2

0 = Not Jog using [Jog Speed 2]
1 = Jog using [Jog Speed 2]

x

Current
Limit Stop

0 = Not Current Limit Stop
1 = Current Limit Stop

x

Coast Stop 0 = Not Coast to Stop

1 = Coast to Stop

x

Spd Ramp
Hold

000 = Spd Ref A
001 = Spd Ref B
010 = Preset 2
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

x

Reserved

x

Spd Ref
Sel0

000 = Spd Ref A
001 = Spd Ref B
010 = Preset 2
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

x

Spd Ref
Sel1

000 = Spd Ref A
001 = Spd Ref B
010 = Preset 2
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

x

Spd Ref
Sel2

000 = Spd Ref A
001 = Spd Ref B
010 = Preset 2
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

x

Reserved